udp.send()

udp.send(sourcePort, dest, payload, encrypted)

Transmits a UDP packet to a host and port.

Please use the latest firmware, On earlier firmware versions the sourcePort was omitted.

Arguments

NameTypeRequiredDefaultDescription
sourcePort yes Source port for UDP datagrams
dest string yes Destination in "host:port" form, e.g. "192.168.5.159:2115".
payload string | object yes Datagram payload data
encrypted bool optional false Whether to use built in AES256 Encryption and integrity validation

Returns

number 0 = success, >0 = error code

Example

// UDP Stream Example

while(run()){

      let payload = {
      batteryVoltage: 15.3,
      uptime: now()
    };

	udp.send(4000,"192.168.5.159:2115",string(payload));
	waitMS(1000);
}