📦 Archived documentation: r1 (committed 2026-10-07) View current documentation →

eip.read()

eip.read(file, offset, bytes) → { status, data }

Reads bytes from a PLC data file.

Reads bytes starting at element offset of the addressed file. Parse the returned buffer with string.seek() and string.read().

Arguments

NameTypeRequiredDefaultDescription
file string yes — File address with type prefix (F,O,I,S,B,T,R,N) + number, e.g. "F103".
offset number yes — Starting element offset within the file.
bytes number yes — Number of bytes to read, e.g. 4*4 for four 32-bit floats.

Returns

object { status, data } — status 0 = success; data is a bin buffer.

Example

let res = eip.read("F103", 1, 4*4); // four 4-byte floats

if(res.status === 0){
  res.data.seek(0); // Position our cursor at the start of the data
  let plc = {
    flow:      res.data.read("F32ABCD"),
    pressure:  res.data.read(), // No format specified, use the last specified format
    pumpSpeed: res.data.read(),
    temp:      res.data.read(),
    lastUpdated: now()
  };
  print(string(plc));
} else {
  print("PLC Read Failed");
}