📦 Archived documentation: r1 (committed 2026-08-05) View current documentation →

mqtt.connect()

mqtt.connect(options) → number

Connects to an MQTT broker and registers topic subscriptions with a callback.

Options object fields:

Field Type Meaning
url string Broker address, e.g. "mqtt://172.16.220.22:1883".
client string MQTT client ID.
subscribe array Topic filters to subscribe, wildcards allowed, e.g. ["power_system/relays/+"].
callback function Called for each received message with an event object { retain, qos, message, topic }.

The callback's event.message can be a JSON string (parse with JSON.parse) or binary data (convert with the bin functions).

Returns 0 on success, 207 if already connected; any other value is an error code.

Arguments

NameTypeRequiredDefaultDescription
options object yes — { url, client, subscribe: [...], callback } — see table.

Returns

number 0 = connected, 207 = already connected, anything else = error code.

Example

function mqttSubscriberCallback(event){
  print("MQTT EVENT: ", string(event));
  // {"retain":false,"qos":0,"message":"Hello World","topic":"power_system/relays/1"}
}

let ret = mqtt.connect({
  url: "mqtt://172.16.220.22:1883",
  client: "Nikiah Repeater",
  subscribe: ["power_system/relays/+"],
  callback: mqttSubscriberCallback
});
print("connect:", ret); // 0 ok, 207 already connected