📦 Archived documentation: r1 (committed 2026-08-05) View current documentation →

run()

run() → boolean

Returns true while the script should keep running; the required condition for every main loop.

Polls the script scheduler. While the script should keep executing, run() returns true; when the device needs the script to stop (for example during a configuration update), it returns false.

Binding your main loop to run() allows the device to stop the script during configuration updates and prevents unexpected behavior. Your script must exit within 5 seconds of run() returning false, otherwise it will not be updated during configuration changes, a device restart will be required, and objects referenced by the script may become undefined.

Calling run() also syncs the IO variables with your local variables — see syncIO() for mid-loop synchronisation.

Returns

boolean true while the script should continue; false when it must shut down.

Example

while(run()){
  // monitoring logic here
  waitMS(100);
}
// falls through here during a configuration update — exit promptly