modbus.read()

modbus.read(port, unitId, fc, startReg, count) → { status, data }

Reads registers or coils from a Modbus slave.

Reads from a connected slave and returns { status, data } where status is 0 on success and data is a binary buffer. Parse the buffer with data.seek(0) then repeated data.read(format) calls.

Arguments

NameTypeRequiredDefaultDescription
port number yes Communication port: 0 = TCP, >0 = Hardware Serial Port (serial ports need serial.init() first).
unitId number yes Slave unit ID.
fc number yes Modbus function code, e.g. 3/4 = read registers. FCs 1/2 return a bit array.
startReg number yes Starting register address, e.g. 0x88B9.
count number yes Number of registers or coils to read.

Returns

object { status, data } — status 0 = success; data is a bin buffer.

Example

let ret = modbus.read(0,       // 0=tcp, >0 = physical serial port
                      1,       // slave unitID
                      4,       // function code
                      0x88B9,  // start register
                      30);     // register count

if(ret.status === 0){
  ret.data.seek(0);
  let data = {
    meanWindSpeed:     ret.data.read("U32DCBA")/10, // m/s
    meanWindDirection: ret.data.read("U32")/10,     // degrees
    airTemp:           ret.data.read("S32")/10,     // °C
  };
  print(string(data));
} else {
  print("Read Failed, err=", string(ret));
}