📦 Archived documentation: r1 (committed 2026-08-05) View current documentation →

setEnv()

setEnv(key, value)

Sets a device environment / configuration variable at runtime.

Adjusts device configuration from within a script. Known keys include:

Key Value Effect
"led" "green", "red", … Sets the front-panel status LED color.
"log.clear" (none) Clears the system log.
"sys.utc_offset" number (hours) Sets the clock's UTC offset, e.g. -8.
"sys.meas_interval" seconds Measurement interval.
"sys.sync_interval" seconds Server upload / sync interval.
"enc.key" string End-to-end encryption passphrase used for communication when encryption is activated. If not set, the device password is used.

A practical use is adapting the measurement interval to communication outages — see the Variable Measurement Interval example, which stretches the interval as the measurement queue (__status().mqueue) fills.

Arguments

NameTypeRequiredDefaultDescription
key string yes — Environment variable name (see table above).
value string | number optional — New value. Some keys, like "log.clear", take no value.

Example

setEnv("led", "green");          // status LED
setEnv("sys.utc_offset", -8);    // Pacific time
setEnv("sys.meas_interval", 60); // measure every minute