eip.handle()

eip.handle(handler)

Answers incoming EtherNet/IP read and write requests from a PLC.

Registers a handler for EtherNet/IP requests arriving at the device. The request object provides:

Field Meaning
req.file The requested file address (e.g. "F103").
req.bytes Read requests: the byte length of the requested data.
req.data Write requests: a bin buffer with the written data. Absent on reads.

Write requests (req.data present): parse the buffer with req.data.seek() / req.data.read() and apply the values — e.g. unpack a PLC status word into individual io flags with bit masks.

Read requests: build a response with bin.alloc() and the buffer write methods (including the "BIT" format for packing status bits), then return the buffer.

Arguments

NameTypeRequiredDefaultDescription
handler function yes — Callback function(req){ … } — return a bin buffer to answer read requests.

Example

eip.handle(function(req){          // handle incoming EtherNet/IP requests
  if(req.data){                    // write request
    req.data.seek(0);
    let status = req.data.read("U16AB");
    io.PALL = {
      feedEnable:  status & 1,
      masterAlarm: (status & (1<<5)) > 0,
      flowAvailable: req.data.read("U16AB") / 0.2777778
    };
  } else {                         // read request — build and return a reply
    let buff = bin.alloc(100);
    buff.write("BIT", [0, io.p304.running, io.p303.running, 0,0,0,0,0, 0,0,0,0,0,0,0,0]);
    buff.write("U16AB", [151.2 * 0.2777778, io.clearwellLevel701.inst * 10]);
    return buff;
  }
});