udp.handle()

udp.handle(port, handler, encrypt)

Listens for UDP packets on a port and passes them to a callback — only one listener is supported.

Registers the device's single UDP listener. The handler receives a request object whose req.data holds the packet payload — parse JSON payloads with JSON.parse(). When encrypt is true, payloads are decrypted with AES-256 and the integrity validated with a SHA256 checksum before the handler runs.

Arguments

NameTypeRequiredDefaultDescription
port number yes — UDP port to listen on, e.g. 9000.
handler function yes — Callback function(req){ … } — req.data is the received payload.
encrypt boolean yes — true to expect AES-256 encrypted payloads.

Example

udp.handle(9000, function(req){   // only a single udp.handle listener is supported
//req = {port:4000,host:"172.16.220.1",data:"{msg:\"Hello World!\"}"}

let data = JSON.parse(req.data);  // parse the received payload as JSON

print(data.msg);
  
}, false); // false: do not use AES-256 encryption or checksums