modbus.setLock()

modbus.setLock(locked) → boolean

Locks/unlocks the slave data table so clients never read a half-updated table.

Lock the table before updating it from your script, then unlock so clients can read and write again. modbus.setLock(true) returns true when the lock was acquired.

Arguments

NameTypeRequiredDefaultDescription
locked boolean yes — true to lock the table, false to unlock.

Returns

boolean true when the lock state was applied.

Example

if(modbus.setLock(true)){
  mbData.seek(0);
  mbData.write("F32BADC", [1,2,3,4,5,6,7,8,9,10,11,12,13,14,15]);
  mbData.write("U32BADC", 23.33);
  modbus.setLock(false);
}